DESCRIPTION
Everpure Insurice PF Series Water Filter Systems (Figures 1-3) are identical to standard
Insurice systems except that the PF Series systems include a 20" sediment prefilter housing
pre-installed and assembled onto the inlet header/manifold assembly. Insurice PF systems
are designed for use in installations with dirtier, cloudier source water and incorporate the
same Everpure Insurice 1⁄2 micron Quick-Change precoat filter cartridges (I2000, I2000
2
, I4000
& I4000
2
) which remove potentially harmful particulates and chlorine taste and odor from the
water while introducing an advanced scale inhibitor. – As tested by Everpure
The replaceable prefilter cartridge element removes larger dirt and rust particles and extends
the life of the sub-micron carbon filters. Thus, ice quality and ice machine performance are
improved while machine downtime, maintenance and energy costs are substantially reduced.
SELECTING A MOUNTING LOCATION
1. Give consideration to the weight of the unit when operating (filled with water). Operating
weights of the Insurice PF Systems are:
• SingleSystem-19lbs.(8.62kg.)
• TwinSystem-35lbs.(15.9kg)
• TripleSystem-45lbs.(20.4kg)
2. The location should allow for:
• Minimumclearanceof2
1
2" under the cartridge(s) so it can be lowered for removal and
replacement.
• Adequatespacefor“in”and“out”waterlineconnections.
• Benearadrainforushing.
OPERATING SPECIFICATIONS*
Combined Model Name
Replacement
Cartridge
Flow Rate Capacity
Insurice PF Single – i2000 i2000 1.67gpm(6.3Lpm) 9,000gal(34,050L)
Insurice PF Single – i2000
2
i2000
2
1.67gpm(6.3Lpm) 9,000gal(34,050L)
Insurice PF Twin – i2000 i2000 3.3gpm(12.6Lpm) 18,000gal(68,100L)
Insurice PF Twin – i2000
2
i2000
2
3.3gpm(12.6Lpm) 18,000gal(68,100L)
Insurice PF Triple – i2000 i2000 5.0gpm(18.9Lpm) 27,000gal(102,150L)
Insurice PF Triple – i2000
2
i2000
2
5.0gpm(18.9Lpm) 27,000gal(102,150L)
Insurice PF Single – i4000 i4000 1.67gpm(6.3Lpm) 12,000gal(45,400L)
Insurice PF Single – i4000
2
i4000
2
1.67gpm(6.3Lpm) 12,000gal(45,400L)
Insurice PF Twin – i4000 i4000 3.3gpm(12.6Lpm) 24,000gal(90,800L)
Insurice PF Twin – i4000
2
i4000
2
3.3gpm(12.6Lpm) 24,000gal(90,800L)
Insurice PF Triple – i4000 i4000 5.0gpm(18.9Lpm) 36,000gal(136,200L)
Insurice PF Triple – i4000
2
i4000
2
5.0gpm(18.9Lpm) 36,000gal(136,200L)
* For individual cartridge specifications, refer to cartridge literature.
Temperature: 35-100°F(2-38°C)
Pressure: 10-125psi(0.7-8.6bar),non-shock
For cold water use only.
Figure 1 – Insurice PF Single System
EV3119-03RevAMR08
Installation and Operation Guide
Insurice PF Filter Systems
ManufacturedbyEverpure
Figure 2 – Insurice PF Twin System
Figure 3 – Insurice PF Triple System
INSTALLATION
1. Usethepredrilledmountingholesinthemanifoldbracketasguides.Markanddrillanchor
holes.Mountsecurely.SeeFigures4-6.
2. Shut off power to ice machine.
3. Connect outlet port of Insurice PF system to equipment served. Always use a NSF approved
pipedopeorTeontapeatallconnections.Useabackupwrenchonallttingswhile
connecting to avoid excessive stress on the system components.
4. Connect minimum 1/2" (3/4" preferred) water line to inlet side of Insurice PF system prefilter.
Do not turn on the supply water yet.
5 Connecttubingtoushingvalveandruntodrain.
Note: Some municipal plumbing codes and good sanitary practices require an air gap at
the drain termination point.
6. Removethewrappingfromthepreltercartridgeandinsertitintotheclearprelterbowl,
aligning the hole in the bottom of the cartridge over the raised stub in the bottom of the
bowl.
7. ChecktoseethattheO-ringisinplaceatthetopoftheprelterbowlandthatitis
lubricated with food grade silicone lubricant. Install the bowl by aligning the hole in the
top of the cartridge with the stub extending down from the housing head and threading the
bowl onto the head. Hand tighten snugly. Do not over-tighten the bowl.
8. RemovethewrappingfromtheInsuricePFltercartridge(s).
9. InstalltheInsuricePFcartridge(s)intotheInsuricePFsystemhead(s)followingdirections
on the cartridge label or as shown in the Cartridge Change illustrations.
10. Turnonwatersupplyandushthecartridge(s)byrunningwaterthroughatfullforcefor
five minutes. This will set the filtering media and purge air and fines, insuring maximum
filter life.
11. Afterushing,closetheushingvalveandturnonpowertoequipment.Seeillustrations.
CARTRIDGE CHANGE DETERMINATION
Replacecartridgeswhencapacityisreached,orwhenowbecomestooslow,butatleast
annually.
The system outlet pressure gauge provides a quick, simple means of determining when the
Insurice PF filter cartridge(s) should be checked. The gauge can be used to monitor dynamic
(owing)pressureandstatic(line)pressure.Theltercartridgesshouldbechangedwhenthe
gauge needle is in the red area while the system is in operation. In multiple cartridge systems,
all filter cartridges should be changed at the same time.
Not for residential use. For food service applications only.
Figure 4 – Insurice PF Single System
25"
14"
INLET
3/8" FNPT
Primary
Filter
Cartridge
Prefilter
(Inside Sump)
Figure5–InsuricePFTwinSystem
Outlet
3/4" FNPT
21.5"
25.59"
INLET
3/4" FNPT
Figure6–InsuricePFTripleSystem
Outlet
3/4" FNPT
INLET
3/4" FNPT
25.75"
29.59"
CARTRIDGE CHANGE PROCEDURE
Everpure Carbon Filter Cartridge
Change
1. Shut off power to equipment.
Shut off inlet water ahead of
system.
2. Openushingvalvetorelieve
pressure.
3. Hold head firmly and push
upward. Turn cartridge to left
until it stops.
4. Pull cartridge downward and
out of head.
5. Holdheadrmly.Aligncartridge
lug with label. Insert new
cartridge firmly into head.
6. Turncartridgeright90˚until
rotation stops.
7. Repeatsteps3-6forremaining
cartridges.
Flushing
8. Withushingvalvefullyopen,
open inlet water at full force
forveminutes.Closeushing
valve.
9. Turnonpowertoequipment
REPLACEMENT PARTS
Contact your local Everpure dealer for filter cartridges or system replacement parts.
CARTRIDGE CHANGE INSTRUCTIONS
1. Shut off the inlet water supply to the system.
2. Makesureanyoutletvalvestoequipmentareclosed.
3. Connectadrainhosetotheushingvalveorplaceabucketunderitsoutlet.
4. Opentheushingvalvetorelievesystempressure.
5. Momentarilydepresstheredpressurereliefvalvebuttonsontopoftheprelterhead.
6. Unthreadandremovetheclearprelterbowlanddumpanywaterfromthebowl.Asumpwrenchisprovidedtoassistinlooseningatight
bowl.Removeanddiscardtheoldpreltercartridge.
7. Rinseandcleanthebowlwithcleanwater.Nospecialcleanersareneeded.
8. CheckandcleanthebowlO-ring.Ifitisdry,lubricateitwithafoodgradesiliconelubricant.Ifitiscrackedordeteriorated,replaceit.
9. RemovethewrappingfromanewEC210preltercartridgeandinsertthecartridgeintotheprelterbowlaligningtheholeinthebottomofthe
cartridge over the raised stub in the bottom of the bowl.
10. ChecktoseethattheO-ringisinplaceatthetopoftheprelterbowlandthatitislubricatedwithfoodgradesiliconelubricant.Reinstallthe
bowl by aligning the hole in the top of the cartridge with the stub extending down from the housing head and threading the bowl onto the
head. Hand tighten snugly. Do not over-tighten the bowl.
11. RemovethewrappingfromthenewInsuriceltercartridge(s).
12. Install the filter cartridge(s) into the filter manifold heads following directions on the cartridge label.
13. Opentheinletwatersupplytothepreltersub-assemblyandushthecartridgesbyrunningwaterthroughthesystematfullforceforve
minutes. This will purge any air and fines and ensure maximum filter life.
14. Shutofftheushingvalveandopenanyoutletvalvestoequipment.
15. Restoretheequipmenttoservice.
Std. No. 42—Aesthetic effects
Chemical Reduction
Taste & Odor
Chlorine
Mechanical Filtration
Nominal Particulate Class I
Std. No. 53—Health effects
Mechanical Filtration
Turbidity (i2000, i2000
2
only)
Cyst
Asbestos (i2000, i2000
2
only)
System Tested and Certified by NSF International against NSF/
ANSIStandard42and53forthereductionof:
Check for compliance with state and local laws and regulations. Do not use with water that is microbiologically unsafe or of unknown quality
without adequate disinfection before or after the system. Systems certified for cyst reduction may be used on disinfected waters that may
contain filterable cysts.
For sales, replacement components, and service, contact your Everpure dealer or:
Everpure, LLC: 1040MuireldDrive•HanoverPark,Illinois60133•800.323.7873
In Europe: Toekomstlaan30•B-2200Herentals,Belguim
In Japan: HashimotoMNBldg.7F•3-25-1HashimotoSagamihara-Shi•Kanagawa229-1103,Japan
PrintedinU.S.A. EV3119-03RevAMR08
Technical Service
800.942.1153
www.everpure.com
LIMITED WARRANTY
COMMERCIAL WATER TREATMENT EQUIPMENT
You have just purchased one of the finest water treatment units made. As an expression of our confidence in Everpure products, this product is warranted
against defects in material and workmanship to the original end-user when installed in accordance with Everpure specifications. The warranty period
commences from the date of purchase and is administered as follows:
For a period of ONE YEAR Replaceable elements (i.e., filter & water treatment cartridges)*
For a period of FIVE YEARS The entire system (excluding replaceable elements)
*This is for material & workmanship, not filter or water treatment cartridge life.
The unit must be used in operating conditions that conform to Everpure’s recommended design guidelines. This warranty will not apply if the unit has been
modified, repaired or altered by someone not authorized by Everpure.
If a part described above is found defective within the specified period, you should notify Everpure technical service at the phone number listed below.
Any part found defective within the terms of this warranty will be repaired or replaced (at Everpure’s discretion) by your local dealer or Everpure technical
service. You pay only freight from our factory and local dealer charges. Any repaired or replaced warranty item will be incorporated under the original
warranty terms of the existing system.
Wearenotresponsiblefordamagecausedbyaccident,re,ood,freezing,ActofGod,misuse,misapplication,neglect,oxidizingagents(suchaschlorine,
ozone, chloramines and other related components), alteration, installation or operation contrary to our printed instructions, or by the use of accessories or
componentswhichdonotmeetEverpure’sspecications.RefertothespecicationssectionintheInstallationandOperatingmanualforapprovedapplication
parameters.
Ourproductperformancespecicationsarefurnishedwitheachwatertreatmentunit.TOTHEEXTENTPERMITTEDBYLAW,EVERPUREDISCLAIMSALL
IMPLIEDWARRANTIES,INCLUDINGWITHOUTLIMITATIONWARRANTIESOFMERCHANTABILITYANDFITNESSFORPARTICULARPURPOSE;TOTHEEXTENT
REQUIREDBYLAW,ANYSUCHIMPLIEDWARRANTIESARELIMITEDINDURATIONTOTHEPERIODSPECIFIEDABOVEFORTHEENTIREWATERTREATMENT
UNIT. As a manufacturer, we do not know the characteristics of your water supply or the purpose for which you are purchasing this product. The quality of
water supplies may vary seasonally or over a period of time, and your water usage rate may vary as well. Water characteristics can also differ considerably
if this product is moved to a new location. For these reasons, we assume no liability for the determination of the proper equipment necessary to meet your
requirements, and we do not authorize others to assume such obligations for us. Further, we assume no liability and extend no warranties, express or implied,
for the use of this product with a non-potable water source or a water source which does not meet the conditions for use described in the owner’s guide or
performancedatasheetforthisproduct.OUROBLIGATIONSUNDERTHISWARRANTYARELIMITEDTOTHEREPAIRORREPLACEMENT(ATEVERPURE’S
DISCRETION)OFTHEFAILEDPARTSOFTHEWATERTREATMENTUNIT,ANDWEASSUMENOLIABILITYWHATSOEVERFORDIRECT,INDIRECT,INCIDENTAL,
CONSEQUENTIAL,SPECIAL,GENERALOROTHERDAMAGES.
Some states do not allow the exclusion of implied warranties or limitations on how long an implied warranty lasts, so the above limitation may not apply to
you. Similarly, some states do not allow the exclusion of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This
warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Consult your telephone directory for your local
independently operated Everpure dealer, or write Everpure for warranty and service information.